Technical
Details
Input
: 220/230 Volts Single Phase
50Hz. Ac supply.
Output
: 10 - 150 KV
KW : 150-1500W
Cooling : Naturally
Air Cooled.
Output
Voltage Control
: Stepless
Rating
: Continuous
for testing duty.
HT CABLE : The
equipment is supplied with five meters long copper braided H.T.
cable with HT plug and socket. The braiding remains on earth
potential.
LT CABLE : For
input supply ten meters long 3 core cable is provided.
ZERO START INTERLOCKING : This
is to ensure that the H.T. shall not actuate if the voltage
control knob is not at zero position.
EARTH INTERLOCKING : If
proper earth is not connected the HT shall not actuate.
AUTO DISCHARGING ARRANGEMENT :
The equipment consists of automatic cable
discharging arrangement.
SOCKET :
H.T. plug and socket has been especially developed by us with
automatic earthing arrangement
METERS : mA
meter and Volt meter are provided on H.T. side. The meters are
well protected against surges and spikes.
OVER VOLTAGE PROTECTION :
H.T. Automatically trips in case of output voltage exceeds the
preset level.
SURGES AND SPIKES PROTECTION :
During the testing surges or spikes are often generated due to
short circuit. The equipment is fully protected against these.
DISCHARGE
ROD : A Discharge rod is
provided with system to discharge residual voltage.
EARTHING
CABLE : Ten meters long
earthing cable is also provided with the unit.
|