Technical
Details
TRANSFORMER :
A double wound step up transformer is the most important part of the equipment. The transformer is wound with high quality enameled copper wire & Polyster film/ Paper is provided between the layers. CRGO step core is used for light weight & efficient
transformer.
VOLTAGE CONTROL :
A step less auto-transformer is used for controlling the output from zero to maximum. The auto-transformer has built in arrangement for zero start interlocking.INPUT VOLTAGE : 230 or 400 V single phase 50 Hz AC
supply.
OUTPUT VOLTAGE : Upto 300 KV
CAPACITY : Upto 1000
KVA
METERING :
Voltmeter to indicate output voltage and Ampere meter to indicate the input current are provided upto 25 KVA on primary side.Voltmeter and Amperemeter are provided are provided on secondary side to indicate output voltage and current for higher capacity
DUTY CYCLE : 15 minutes ON / 15 Minutes OFF
TERMINATION
: One end at earth potential & other at HV
insulator.
CONTROL
:
-
Knob to control the output voltage from zero to maximum or push button n
case of motorized
units.
-
Knob to preset
timer.
-
Knob to for tripping current
control.
PROTECTION
:
-
Rotary switch and fuse upto 25 KVA. Switch fuse unit is provided for higher
-
capacity.
-
A fast acting DC relay actuates to isolate High voltage in case of fault or
-
when current exceeds the preset
value.
-
The unit has zero start interlocking arrangement to ensure that HV will not
-
actuate unless variac is at zero
position.
-
Test cage door interlock where-ever
required.
ADDITIONAL
:
-
The units upto 10 KVA are housed in single housing above 10 FEATURES KVAare supplied two or more parts as per
capacity.
-
Model upto 25 KVA will keep on indicating the voltage at which the sample
under test has failed since the meter is on primary side.The control panel in
all the models is naturally air cooled type. Control transformer and maintransformer oil or air cooled as per the design & capacity of the unit.